Jiangsu Acrel Electrical Manufacturing Co., LTD.
Jiangsu Acrel Electrical Manufacturing Co., LTD.

Application of Intelligent Control and Wireless Temperature Monitoring Products in Sepang Thermal Power Station Project of Lee & Man Paper, Malaysia

Overview

Substation operating equipment such as busbars, cables and circuit breakers operates continuously under high-voltage and heavy-current conditions. Temperature monitoring and maintenance of such equipment constitute an indispensable part to ensure reliable power grid operation. Especially for enclosed equipment including high-voltage switchgear and gas-insulated switchgear (GIS), heat dissipation is inherently poor. Routine manual temperature measurement cannot achieve direct and online temperature monitoring of components inside cabinets. Owing to the lack of effective online temperature monitoring and early-warning systems, fires caused by overheated substation equipment have been frequently reported in recent years. Such incidents severely impair power supply reliability, bring substantial economic losses to power utilities, and may even result in personal injury or fatalities.



lee-man-paper-malaysia 01.png


Lee & Man Paper has invested in four 5600/900 packaging paper machine production lines (PM23, PM25, PM26 and PM27) at its Sepang paper manufacturing base in Malaysia, with an average daily pulp output of 1,000 tonnes. The captive power plant supporting the production lines is under steady construction. The gas turbine installation works for Phase II captive thermal power plant involve two sets of 30 MW gas turbines and associated auxiliary facilities.



lee-man-paper-malaysia 02.png


A stable and reliable power system serves as a vital foundation for enterprise development. Therefore, adopting rational, effective and dependable temperature measurement technology to conduct real-time online monitoring of heat-prone locations such as current transformers, busbars, cables and switch contacts is of great significance. It enables timely detection and alarm of abnormal temperature risks so as to guarantee reliable operation of substation equipment.


Product Requirements and Configuration

The project implements safety temperature monitoring, measurement and control for 67 high-voltage cabinets in the thermal power station, including incoming cabinets, PT cabinets and outgoing cabinets. Wireless temperature monitoring and intelligent control products are required. Detailed specifications are listed below:

1.Dynamic mimic diagram, high-voltage live display and interlock control;

2.Energy storage indication, live voltage and anti-misoperation voice prompt;

3.Two-channel automatic temperature & humidity control and display; communication cable length: 6 m;

4.Remote/local control and switch closing/opening operation;

5.Cabinet lighting control;

6.RS485 / Modbus communication interface;

7.Human body induction function;

8.Pre-close / pre-open flashing indication;

9.Temperature measurement and display for electrical contacts; 6 temperature measuring points per high-voltage cabinet;

10.Wireless transmission with energy harvesting power supply; starting current ≥5 A; measuring range: -50℃ ~ 125℃; integrated sensor and power supply module; service life ≥10 years; measurement accuracy: ±1℃;

11.Real-time monitoring: temperature sensors transmit real-time temperature data to receivers. Receivers forward data to intelligent control units (upload frequency configurable), which further transmit data to the background system to guarantee real-time data acquisition.

In accordance with the above requirements, Acrel wireless temperature monitoring products are selected as shown in the table below.


Product Solution List



On-site Installation

lee-man-paper-malaysia 05.png


Temperature Monitoring Scheme

Wireless temperature monitoring for electrical contacts inside high/low-voltage cabinets (local centralized display)


lee-man-paper-malaysia 06.png


Related Products

Four types of wireless temperature sensors are available: (a. Battery-powered type; b. Current energy harvesting type)

model

figure

Parameter Description

Installation method

ATE100M

32.4*32.4*16mm; -50C~+125°C,accuracy ±1°C, battery powered,5-year lifespan; 470MHz,150-meter range in open terrain.

Magnetic fixation

ATE100


62.4*32.4*16mm, 13.5mm (length*width*height, aperture); -50°C~+125°C, accuracy ±1°C, battery powered, lifespan ≥5 years; 470MHz, open-field range 150 meters.

Bolt fixing

ATE200


35*35·17mm, L=330mm (length*width·height, strap); -50°C~+125°C, accuracy ±1°C; battery powered, lifespan ≥5 years; 470MHz, open-air range 150 meters.

watch strap binding

ATE100P





62.4*32.4*16mm, 13.5mm (L*W*H, aperture); -50°C~+150°C, accuracy ±0.5°C, battery powered, lifespan ≥5 years; 470MHz, open-field range 150 meters; protection rating IP68

Bolt fixing

ATE200P

35*35*17mm,L=330mm (length*width*height of the strap); -50°C~+150°C, accuracy ±0.5°C; battery powered, lifespan ≥5 years; 470MHz, 150-meter range in open field; IP68 protection rating.

watch strap binding

ATC600

90*90*38mm (Length*Width*Height); AC/DC 85~265V power supply; ATC600 has two working modes: Terminal (-C) and Repeater (-Z), which can be selected according to project layout.

It can receive temperature readings from up to 240ATE100/ATE100M/ATE200/ATE400/ATE100P/ATE200P wireless temperature sensors; one-way uplink RS485 interface; Modbus protocol.

Din rail installation


Conclusion

ASD320 and ASD100G intelligent control devices are new multi-functional intelligent mimic indication units specially designed for power switchgear. They integrate multiple functions including primary circuit mimic diagram, switch status, circuit breaker position, earthing switch position, spring energy storage status, disconnector status, voice anti-misoperation prompt, high-voltage live indication, wireless temperature measurement, high-voltage live interlock, automatic heating & dehumidification control, temperature and humidity regulation, heater fault indication and over-temperature alarm. These functions support safe and reliable electrical operation.